SCALE 1:1 STD NEC · IEC · AS/NZS · ACI · AISC
B
CodePass.PRO
Engineering Calculators
SHEET 71 / 79
Reference · Conversion · NEC 310.16 · Cu / Al

Wire Sizing for Amps — AWG to Ampacity Chart Reference

Wire sizing for amps follows a one-line lookup in NEC Table 310.16 — pick the smallest AWG whose 75 °C column ampacity meets or exceeds the load (after the 1.25× continuous-load factor). This page tabulates copper and aluminum ampacity from 14 AWG to 4/0, lists the breaker-to-wire-size ladder, covers the small-conductor rule (NEC §240.4(D)), and walks through a worked example for a 100 A residential service. Reviewed by a licensed PE.

Wire ampacity calculator

The wire-size calculator picks the smallest NEC-listed conductor that satisfies both ampacity (NEC 310.16) and voltage-drop limits in one pass. Enter voltage, load current, run length, conductor material, ambient temperature, and number of CCCs in the same conduit; the tool returns the right copper or aluminum AWG along with the IEC mm² equivalent for international projects.

→ Wire size calculator  ·  → Amp to wire size chart  ·  → Voltage drop calculator

Wire ampacity formulas

Eq. 01 — Required ampacity (continuous + non-continuous) SI
Irequired=1.25Icont+InoncontI_{required} = 1.25 \cdot I_{cont} + I_{non-cont}
·
I_cont = continuous load (3+ hr at full value)
·
I_non-cont = non-continuous load
·
NEC §210.20(A) for branch circuits, §215.3 for feeders
Eq. 02 — Adjusted ampacity (NEC 310.15) SI
Iadj=ItablekTkfillI_{adj} = I_{table} \cdot k_T \cdot k_{fill}
·
I_table = NEC Table 310.16 base ampacity (75 °C column typical)
·
k_T = ambient-temperature correction factor
·
k_fill = conduit-fill factor for > 3 CCCs (1.0, 0.80, 0.70, 0.50…)
Eq. 03 — Small-conductor rule (NEC §240.4(D)) SI
Ibreaker{15,20,30} A for {14,12,10} AWG CuI_{breaker} \leq \{15, 20, 30\} \text{ A for } \{14, 12, 10\} \text{ AWG Cu}
·
14 AWG Cu — max 15 A breaker regardless of ampacity column
·
12 AWG Cu — max 20 A; 12 AWG Al — max 15 A
·
10 AWG Cu — max 30 A; 10 AWG Al — max 25 A
Eq. 04 — Voltage drop, single-phase or DC SI
Vd=2LIRac1000V_d = \frac{2 \cdot L \cdot I \cdot R_{ac}}{1000}
·
L = one-way length (m)
·
I = load current (A)
·
R_ac = AC resistance per km (Ω/km, NEC Chapter 9 Table 9)
·
Limit: V_d / V_source ≤ 3 % branch / 5 % combined

Standards governing wire ampacity

DocumentScope
NFPA 70 (NEC) Article 310Conductor ampacity tables 310.15, 310.16, 310.17, 310.20
NEC §240.4 / §240.4(D)Conductor protection — small-conductor rule
NEC §210.20 / §215.3Continuous-load factor 1.25× for branch and feeder
UL 83 / UL 854THHN/THWN and SE service-entrance cable
UL 44Thermoset-insulated wire (RHH/RHW, XHHW-2)
IEEE Std 141 (Red Book)Industrial cable selection methodology
IEC 60364-5-52International cable selection — current-carrying capacity
AS/NZS 3008.1.1Australian / New Zealand cable selection tables

Reference: copper wire ampacity (NEC Table 310.16, 75 °C)

AWG60 °C (A)75 °C (A)90 °C (A)NEC §240.4(D) max breaker
1415202515 A
1220253020 A
1030354030 A
8405055
6556575
4708595
385100110
295115130
1110130150
1/0125150170
2/0145175195
3/0165200225
4/0195230260
250 kcmil215255290
500 kcmil320380430

Reference: aluminum wire ampacity (NEC Table 310.16, 75 °C)

AWG60 °C (A)75 °C (A)90 °C (A)NEC §240.4(D) max breaker
1215202515 A
1025303525 A
8304045
6405060
4556575
3657585
27590100
185100115
1/0100120135
2/0115135150
3/0130155175
4/0150180205
250 kcmil170205230
500 kcmil260310350
  1. Compute the load amperes For lighting and outlets, sum the maximum simultaneous load. For motors, use NEC Table 430.250 (3-phase) or 430.248 (1-phase) FLA. For HVAC, use the nameplate MCA per NEC §440.4. For continuous loads (3+ hr at full value), multiply by 1.25.
  2. Pick the conductor material and temperature column Copper is more conductive per cross-section; aluminum is cheaper for large sizes (≥ 4 AWG service entrances). Read NEC Table 310.16 in the 75 °C column unless the entire termination chain (lugs, breakers, splices) is rated 90 °C. The 60 °C column applies only to small conductors and old equipment.
  3. Find the smallest AWG meeting the ampacity demand For 50 A copper THWN-2 in raceway: read down the 75 °C column to find 50 A — that's 8 AWG. For aluminum at the same load: 6 AWG (50 A at 75 °C). For free air or single conductors in tray, read NEC Table 310.17 instead of 310.16.
  4. Apply ambient and conduit-fill corrections Ambient > 30 °C → multiply by Table 310.15(B)(1) factor. More than 3 current-carrying conductors in raceway → multiply by Table 310.15(C)(1) factor. The corrected ampacity must still meet or exceed the load demand.
  5. Verify voltage drop NEC Fine Print Note recommends voltage drop ≤ 3 % on a branch and ≤ 5 % combined. Use the voltage-drop calculator with conductor R from NEC Chapter 9 Table 9 or the simple R = ρL/A formula. Long runs often dictate up-sizing beyond the ampacity-driven choice.

Worked example — 100 A residential service entrance

A 100 A overhead service to a single-family home. Pick the conductor.

  1. Required ampacity: 100 A continuous; per NEC §215.3, 1.25 × 100 = 125 A.
  2. Aluminum SE cable, 75 °C: 1/0 AWG = 120 A — too small. Use 2/0 = 135 A. ✓
  3. Copper alternative: 3 AWG = 100 A (just meets 100 A demand without the 1.25× factor) — acceptable for service-entrance because NEC §310.12 allows the unadjusted ampacity for residential services up to 400 A.
  4. Final selection: 2 AWG aluminum SE-U cable (most common stocked for 100 A residential).

Comparison — copper vs. aluminum wire sizing

AspectCopperAluminum
Conductivity5.96 × 10⁷ S/m3.77 × 10⁷ S/m
Per-A cross-section1.0× (baseline)~1.6× (one AWG larger)
Cost per ampere2–3× aluminumLowest
Weight per ampereHeavier~50 % of copper for same A
Termination concernsNone specialAnti-oxidant paste, listed lugs (CO/ALR)
Best forBranch circuits, motor leads, control wiringService-entrance, sub-panel feeders, large feeders > 4 AWG

Variants and related queries

Gauge wire amp — common breaker / wire pairings

The dominant breaker-to-wire pairings: 15 A → 14 AWG Cu; 20 A → 12 AWG Cu; 30 A → 10 AWG Cu; 40 A → 8 AWG Cu; 50 A → 8 AWG Cu (90 °C col., 60-A range OK with 6 AWG); 60 A → 6 AWG Cu; 100 A → 3 AWG Cu / 1 AWG Al; 200 A → 3/0 Cu / 250 kcmil Al. The site amp-to-wire chart gives the full ladder.

Wire amp rating chart

Industry-standard wire amp rating charts come from NEC 310.16 (US), IEC 60364-5-52 (international), and AS/NZS 3008 (Australia/NZ). Each table differentiates by conductor material (Cu / Al), insulation temperature rating (60 / 75 / 90 °C in US; 70 / 90 °C in IEC), and installation method (raceway / direct burial / free air). Always cite which table the rating comes from in the design package.

What gauge wire for 80 amp

For an 80 A circuit, 4 AWG copper (85 A at 75 °C) or 2 AWG aluminum (90 A at 75 °C). At the standard 1.25× continuous-load factor, the required ampacity is 100 A, which would push the copper choice up to 3 AWG (100 A); for non-continuous loads (such as cooking ranges), 4 AWG suffices.

Wire ampacity calculator and 4 wire ampacity

"4 wire ampacity" usually refers to the NEC Table 310.15(C)(1) adjustment for > 3 CCCs in conduit: 4 conductors → 0.80 factor (20 % derate); 7–9 → 0.70; 10–20 → 0.50. The neutral counts toward CCC count if it carries unbalanced current (e.g. on 4-wire wye lighting circuits with substantial harmonic content). Equipment grounding conductors do NOT count.

Frequently asked questions

What size wire for a 100 amp service?
For a 100 A residential service: 3 AWG copper or 1 AWG aluminum (both rated 100 A at 75 °C in NEC Table 310.16). For aluminum service-entrance cable (SE-U or SE-R), 1 AWG is the standard. For underground 100 A feeder (USE-2 / SER), use 2/0 AWG aluminum or 1/0 aluminum if the temperature column allows. Most utility supply tables list 1/0 aluminum for 100 A overhead and 2/0 for underground.
What gauge wire for 100 amp sub-panel?
Same as above — 3 AWG copper or 1 AWG aluminum for the feeder between the main panel and the sub-panel. Add 0.5 in voltage-drop margin per 50 ft of run if voltage drop matters for connected appliances. Most residential 100 A sub-panel installs in detached buildings use 4-conductor SER 1/0-1/0-1/0-#2 aluminum (3 phases + neutral, with separate equipment grounding conductor in PVC conduit).
What size aluminum wire for a 100 amp service?
1 AWG aluminum or 1/0 aluminum, depending on the temperature rating of the conductor and terminations. NEC Table 310.16 75 °C column: 1 AWG aluminum is rated 100 A; 1/0 aluminum is rated 120 A. Most utilities and service-entrance suppliers stock 1/0 aluminum SE cable for 100 A residential services because it has a small built-in margin.
What size wire for a 30 amp circuit?
10 AWG copper (rated 30 A at 60/75 °C in NEC Table 310.16) is the standard choice for a 30 A circuit. NEC §240.4(D) "small conductor rule" caps 10 AWG at 30 A regardless of temperature column. For 30 A aluminum: 8 AWG. Common applications include electric dryers (NEMA 14-30), tankless water heaters, and small EV chargers.
What gauge wire for a 20 amp circuit?
12 AWG copper for 20 A (rated 25 A at 75 °C, capped at 20 A by NEC §240.4(D) small-conductor rule). 10 AWG aluminum for 20 A in aluminum-only installations. Used for kitchen and bathroom outlet branches, garage circuits, and any general-purpose branch where appliances may approach the breaker limit.
What size wire for a 60 amp breaker?
6 AWG copper (rated 65 A at 75 °C in NEC Table 310.16) or 4 AWG aluminum (75 A). The 65 A copper ampacity exceeds the 60 A breaker rating — required by NEC §240.4. Common uses: 50 A EV charger sub-panel feeders, hot tub sub-panels, mid-size A/C condensers, range / dryer combinations.

Historic source — the AWG system

The AWG ladder uses a geometric progression — each step decreases the diameter by a constant factor (≈ 1.123) — so going six AWG sizes apart halves the cross-sectional area and doubles the resistance. This is why every electrician memorises the 6-AWG / 2× rule of thumb.

J. R. Brown / Brown & Sharpe — proprietary wire-gauge sizing → 1857 — first published as Brown & Sharpe wire gauge; standardised as American Wire Gauge in NEC by the early 20th century

Related calculators and references

Sources and further reading

  1. NFPA 70 — NEC, Article 310, §240.4, §210.20, §215.3, §310.12 (2023 edition).
  2. UL 83 — Thermoplastic-Insulated Wires and Cables.
  3. UL 854 — Service-Entrance Cables.
  4. IEEE Std 141 — Recommended Practice for Electric Power Distribution for Industrial Plants (Red Book).
  5. IEC 60364-5-52 — current-carrying capacity of cables.
  6. AS/NZS 3008.1.1 — Australian / New Zealand cable selection tables.