SCALE 1:1 STD NEC · IEC · AS/NZS · ACI · AISC
B
CodePass.PRO
Engineering Calculators
SHEET 05 / 79
Calculator · Electrical · NEC 310.16 · Cu + Al

Amp wire chart — AWG and mm² for 15 to 800 A circuits

A complete amp chart for wire — copper and aluminium ampacity by amp rating and AWG / mm², covering branch circuits from 15 A through 800 A service. Includes household and appliance examples, length and voltage-drop guidance, and a live calculator that applies NEC derating automatically. Reviewed by a licensed PE.

Use the calculator

The chart below is the NEC 310.16 standard lookup. The calculator applies all derating (continuous load, ambient, conductor count, parallel sets) and runs the voltage-drop check, so you get the smallest size that passes both tests for your actual installation.

CALC.003 Wire Size · NEC 310.16 · 6 presets · ampacity + VD

NEC 210.19(A) recommends ≤3% VD on branch, ≤5% combined feeder + branch.

°C
A
W
V
cos φ
m
%
Recommended size
12 AWG
Both ampacity and voltage drop pass with margin.
3%
0%3%6%
Voltage drop
— V (—%)
Ampacity (derated)
Required ampacity
Recommended OCPD
Min EGC (NEC 250.122)
Power loss in run
— W
V at load
— V
PASS · NEC 310.16 + 210.19(A)
A_min = max( A_vd , A_ampacity ) · NEC 310.16 NEC 240.4(D) · 250.122 · 310.15(B)
NEC 310.16 — copper conductor ampacity (75 deg C) 14 AWG 15 A 12 AWG 20 A 10 AWG 30 A 8 AWG 40 A 6 AWG 60 A 3 AWG 100 A 2/0 AWG 200 A 4/0 AWG 400 A 350 kcmil 600 A conductor (proportional dia.) 0 amps
Figure 1 — Wire ampacity chart per NEC 310.16: AWG sizes mapped to current ratings (Cu, 75 deg C)

NEC 310.16 amp-to-wire chart

Standard ampacity at 30°C ambient with no more than three current-carrying conductors in a raceway, no continuous-load adjustment. For continuous loads (≥3 hours at full current), divide the table value by 1.25 to get the breaker rating, or pick the next size up so the conductor's ampacity ≥ 1.25 × load.

NEC 310.16 ampacity (≤3 ccc, 30°C ambient) — Cu + Al
SOURCE · NFPA 70 (NEC) 2023, Table 310.16
AWG / kcmilmm²Cu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
142.08152025
123.31202530152025
105.26303540253035
88.37405055354045
613.30556575405055
421.2708595556575
326.785100115657585
233.6951151307590100
142.411013014585100115
1/053.5125150170100120135
2/067.4145175195115135150
3/085.0165200225130155175
4/0107.2195230260150180205
250 kcmil127215255290170205230
300 kcmil152240285320195230260
350 kcmil177260310350210250280
400 kcmil203280335380225270305
500 kcmil253320380430260310350
600 kcmil304350420475285340385
700 kcmil355385460520310375425
750 kcmil380400475535320385435
800 kcmil405410490555330395450

The ampacities for conductors rated 0 through 2000 V shall be as specified in the Allowable Ampacity Table 310.16 through Table 310.20… Where the ambient temperature is other than 30°C (86°F), the ampacities shall be corrected by the factors in Table 310.15(B)(1)(1) for ambient temperature.

NFPA 70 (NEC) 2023 Edition → Article 310.15(B)(1) Ampacity Tables — Ambient Temperature Correction

How to read the chart, step by step

  1. Get the load current. Read the nameplate full-load amps (FLA) of the equipment, or compute from the load: I = P / V (DC), I = P / (V·cos φ) (1-phase), I = P / (√3·V·cos φ) (3-phase). For motors, use the NEC 430 table FLA, not the nameplate, when sizing branch wire.
  2. Apply the continuous-load factor if applicable. NEC 210.19(A) — if the load runs ≥3 hours at full current (HVAC, EV chargers, lighting, water heaters), multiply by 1.25. The wire must carry this adjusted current after derating. EV chargers are explicitly continuous: a 32 A charger needs a 40 A breaker.
  3. Pick the insulation column that matches your equipment terminations. NEC 110.14(C) caps the effective rating to 60°C for most circuits ≤100 A unless the device is listed for higher; for >100 A circuits and modern equipment, the 75°C column is the practical limit. The 90°C column is used as a starting point for derating math, not for direct sizing.
  4. Look up the AWG that meets the derated ampacity. Find the smallest size in NEC Table 310.16 (or the chart on this page) whose tabulated ampacity, after multiplying by ambient and conductor-count correction factors, ≥ adjusted load. Verify against NEC 240.4(D) — 14/12/10 AWG copper is capped at 15/20/30 A regardless of insulation.
  5. Cross-check voltage drop on the chosen size. For runs longer than ~30 m at 240 V or ~15 m at 120 V, check that V_drop = 2·L·I·ρ/A ≤ 3% branch (5% combined). If voltage drop fails, step up one or more sizes. The calculator embedded above runs this check automatically.
  6. Pick the breaker and the equipment grounding conductor. Round the load up to the next standard breaker per NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 A. Look up the minimum EGC from NEC Table 250.122 based on that breaker rating, not the wire size.

Standard household and small-commercial circuits

Most US residential branch circuits are one of the standard amperages below. The wire size assumes 75°C copper, ≤30 m one-way run, ≤3 conductors in conduit. Always size up if voltage drop on your run exceeds 3%.

BreakerMin Cu wireMin Al wireTypical use
15 A14 AWGLighting, general-purpose receptacle circuits in older homes
20 A12 AWG10 AWGKitchen counter, bathroom, garage, laundry receptacles
30 A10 AWG8 AWGElectric clothes dryer (240 V), small water heater, baseboard heat run
40 A8 AWG6 AWGElectric range branch, small subpanel feeder
50 A8 AWG (6 AWG safer)6 AWGElectric range, EV charger Level 2, welder, hot tub
60 A6 AWG4 AWGSubpanel feeder for detached garage / workshop, large EV charger
100 A3 AWG (2 AWG common)1 AWG (1/0 common)Subpanel for accessory dwelling, small main service
125 A2 AWG1/0 AWGSubpanel feeder for medium load
150 A1 AWG2/0 AWGSubpanel for larger building
200 A2/0 AWG4/0 AWGStandard residential main service in most US homes
400 A600 kcmil1000 kcmilLarge home with EV + heat pump + workshop

Two important caveats: NEC 240.4(D) caps the breaker on 14, 12, and 10 AWG copper at 15, 20, and 30 A even if the insulation rating allows higher. And NEC 310.12 has a special reduced-ampacity rule for 100–400 A dwelling-unit service entrances and feeders supplying the entire dwelling — 4 AWG Cu / 2 AWG Al for 100 A, 2/0 Cu / 4/0 Al for 200 A.

Wire size for major appliances

Each appliance below has its own typical breaker and wire size. Always read the nameplate — actual current draw varies by model, especially for heat-pump and inverter-driven equipment.

ApplianceVoltageTypical ampsBreakerCu wire
Electric clothes dryer240 V24–3030 A10 AWG (3-cond + GND)
Electric water heater (50 gal)240 V1930 A10 AWG
Electric range / oven combo240 V35–5050 A6 AWG
Built-in oven only240 V20–3030–40 A10 or 8 AWG
Built-in cooktop only240 V20–4040 A8 AWG
Central air conditioner (3 ton)240 V15–2530–40 A10 or 8 AWG (per nameplate MCA)
Heat pump (3 ton + strip heat)240 V25–4050–60 A6 AWG
EV charger Level 2 (32 A continuous)240 V32 cont. → 40 OCPD40 A8 AWG
EV charger Level 2 (48 A continuous)240 V48 cont. → 60 OCPD60 A6 AWG
Welder (200 A MIG, 50 A duty)240 V5050 A8 AWG (6 AWG for long runs)
Hot tub / spa240 V40–5050 A GFCI6 AWG (2-cond + GND in conduit)
Tankless electric water heater240 V75–1252 × 60 A or 1 × 150 A6 AWG / 1 AWG

For continuous loads — anything that runs ≥3 hours at full current — NEC 210.19(A) requires the conductor's ampacity to be ≥1.25 × the load. EV chargers are continuous; that is why a 32 A charger needs a 40 A breaker (32 × 1.25), not a 30 A one. The calculator handles this factor automatically when you pick the EV-charging or "continuous" preset.

How length and voltage drop change the answer

The chart sets the absolute floor — the smallest wire that can safely carry the current as heat. On almost every real installation, voltage drop pushes you to a larger wire, especially at 120 V or DC, and on long runs of small wire.

CircuitRun (m)Min Cu (chart)Cu for 3% dropCu for 2% drop