Voltage drop calculator
Calculate voltage drop for DC, single-phase and 3-phase circuits. Built into NEC 2023 and AS/NZS 3008.1.1 limits, with copper and aluminium conductors. Free, no signup, math fully explained. Reviewed by a licensed PE.
Use the calculator
Enter your load current, conductor length, wire size and system voltage. Result updates live with NEC compliance check.
- Drop ratio
- —
- V at load
- —
- Power loss
- —
- ρ used (T-corrected)
- —
What is voltage drop?
When current flows through a conductor, the conductor's own resistance causes a small portion of the source voltage to be lost. That lost voltage is the voltage drop. The longer the wire, the higher the current, or the smaller the conductor, the more voltage is lost — and the less reaches your load.
In the circuit above, a 12 V source pushes 20 A through 30 m of 10 AWG (5.26 mm²) copper wire to a load. The wire's resistance dissipates 3.99 V (33% of source) before the load — meaning the load only sees about 8.0 V. For a 12 V DC system, this is a serious problem: motors stall, LEDs dim, electronics malfunction. Use the online calculator above to find the minimum wire size that keeps drop within acceptable limits.
The voltage drop formula
- V
- voltage drop, V
- L
- one-way conductor length, m
- I
- current, A
- ρ
- resistivity (material), Ω·mm²/m
- A
- cross-sectional area, mm²
- V
- line-to-line drop, V
- L
- length, m
- I
- line current, A
- Z
- impedance, mΩ/m
Resistivity values to use:
| Material | ρ (Ω·mm²/m) | Where used |
|---|---|---|
| Copper (Cu) | 0.0175 | Branch circuits, panels, residential |
| Aluminium (Al) | 0.0280 | Service entrance, large feeders |
How to calculate voltage drop, step by step
- Identify the load current. From nameplate, or compute from VA / V for AC equipment. Use full-load amps (FLA), not rated amps.
- Measure the one-way conductor length. From source (panel/breaker) to the farthest load. Do not double — the formula already accounts for the return path.
- Choose conductor material and size. Copper or aluminium; pick from standard wire sizes (AWG / mm²). Material affects resistivity ρ.
- Apply the formula. Vdrop = 2 · L · I · ρ / A. Use ρ_Cu = 0.0175 Ω·mm²/m, ρ_Al = 0.028 Ω·mm²/m.
- Check against the standard. NEC: ≤3% branch / ≤5% total. AS/NZS 3008: ≤5% from main switchboard.
- If exceeded — increase wire size. Step up one or two sizes; recalculate. Or shorten the run, or use a higher system voltage.