SCALE 1:1 STD NEC · IEC · AS/NZS · ACI · AISC
B
CodePass.PRO
Engineering Calculators
SHEET 09 / 79
Calculator · Electrical · Cooper Bussmann · IEEE 141 · NEC 110.9

Short circuit current calculator

Cooper Bussmann point-to-point method. Computes SCA at the transformer secondary, derated by cable run to the fault point, with optional motor contribution. Recommends the minimum AIC rating for the breaker at that location. Reviewed by a licensed PE.

Use the short circuit calculator

Enter your transformer kVA, secondary voltage, and %Z (or pick a NEMA preset), then optionally add the cable run length to the fault point and motor contribution. The calculator outputs SCA at the transformer secondary, the derating along the cable, the total fault current at the fault, and the recommended breaker AIC.

CALC.005 Short Circuit · Point-to-Point · NEMA + IEEE 141
kVA
%
V
kA
m
A

Standard NEMA practice: motor contribution ≈ 4× connected motor FLA. Set length 0 for fault at the transformer secondary terminals (worst case).

Short-circuit current at fault point
— kA
SCA at transformer terminals; cable derating reduces it downstream.
SCA at transformer secondary
— A
Cable derating factor M
SCA at fault (no motor)
— A
Motor contribution
— A
Total fault current
— A
Recommended AIC
— kA
PASS · 22 kA AIC SUFFICIENT
FORMULA · I_sec = (kVA × 1000) / (√3 × V × %Z/100) SOURCE · COOPER BUSSMANN · IEEE 141
Short circuit current waveform — asymmetrical fault t I Current (A) Time (cycles) 0 1 2 3 4 5 normal load FAULT I_asym (peak) I_sym (steady) DC offset envelope pre-fault asymmetrical decay back to symmetrical
Figure 1 — Short circuit current waveform: asymmetrical peak at fault, then DC decay to symmetrical I_sym

The short circuit current formula

The Cooper Bussmann point-to-point method evaluates fault current in two stages: at the transformer secondary terminals (worst case), then derated downstream by the impedance of each cable run between transformer and fault.

Eq. 01 — SCA at transformer secondary (3-phase, infinite primary bus) SI · Cooper Bussmann SPD
Isec=kVA10003VLL%Z100I_{sec} = \frac{kVA \cdot 1000}{\sqrt{3} \cdot V_{LL} \cdot \frac{\%Z}{100}}
I_sec
symmetrical RMS short-circuit current at xfmr terminals, A
kVA
transformer rating, kVA
V_LL
secondary line-to-line voltage, V
%Z
transformer impedance from nameplate, %
Eq. 02 — Cable derating multiplier (point-to-point) SI · Per-unit impedance method
M=ZxfmrZxfmr+ZcableIfault=MIsecM = \frac{Z_{xfmr}}{Z_{xfmr} + Z_{cable}} \qquad I_{fault} = M \cdot I_{sec}
M
derating multiplier (0 < M ≤ 1), —
Z_xfmr
transformer impedance referred to secondary, Ω
Z_cable
cable resistance to fault point = ρ·L/A, Ω
Eq. 03 — Single-phase variant SI · Cooper Bussmann SPD
Isec,1ϕ=kVA1000V%Z100I_{sec, 1\phi} = \frac{kVA \cdot 1000}{V \cdot \frac{\%Z}{100}}
I_sec, 1φ
single-phase SCA — no √3 factor, A
V
secondary voltage (line-to-neutral or line-to-line as appropriate), V