Short circuit current calculator
Cooper Bussmann point-to-point method. Computes SCA at the transformer secondary, derated by cable run to the fault point, with optional motor contribution. Recommends the minimum AIC rating for the breaker at that location. Reviewed by a licensed PE.
Use the short circuit calculator
Enter your transformer kVA, secondary voltage, and %Z (or pick a NEMA preset), then optionally add the cable run length to the fault point and motor contribution. The calculator outputs SCA at the transformer secondary, the derating along the cable, the total fault current at the fault, and the recommended breaker AIC.
Standard NEMA practice: motor contribution ≈ 4× connected motor FLA. Set length 0 for fault at the transformer secondary terminals (worst case).
- SCA at transformer secondary
- — A
- Cable derating factor M
- —
- SCA at fault (no motor)
- — A
- Motor contribution
- — A
- Total fault current
- — A
- Recommended AIC
- — kA
The short circuit current formula
The Cooper Bussmann point-to-point method evaluates fault current in two stages: at the transformer secondary terminals (worst case), then derated downstream by the impedance of each cable run between transformer and fault.
- I_sec
- symmetrical RMS short-circuit current at xfmr terminals, A
- kVA
- transformer rating, kVA
- V_LL
- secondary line-to-line voltage, V
- %Z
- transformer impedance from nameplate, %
- M
- derating multiplier (0 < M ≤ 1), —
- Z_xfmr
- transformer impedance referred to secondary, Ω
- Z_cable
- cable resistance to fault point = ρ·L/A, Ω
- I_sec, 1φ
- single-phase SCA — no √3 factor, A
- V
- secondary voltage (line-to-neutral or line-to-line as appropriate), V